amprobe
Australia [Change Country]
Home  |  Products  |  Power Quality, Insulation and Ground Resistance Testers   |  Power Quality  |  
Contact usRefer this page

Amprobe DM-III Multitest 1000A Power Quality Recorder

Click here to watch video

Amprobe DM-III Multitest 1000A Power Quality Recorder
Amprobe DM-III Multitest 1000A Power Quality Recorder
Amprobe DM-III Multitest 1000A Power Quality Recorder
Amprobe’s full-featured Three-Phase Power Quality Recorders provide the essential functions and capabilities required to operate accurately and effectively in today’s demanding electrical environments.

Application Notes
  • True RMS (TRMS)
  • Measures and Records Broad Spectrum of Power Quality Parameters: AC Current, AC Voltage to 600V including Sags and Surges, Harmonics (THD and individual up to 49th), Active, Reactive and Apparent Power & Energy, Peak Demand, Power Factor, Frequency measur
  • Compatible with wide range of Current Transducers
  • Comes as a complete kit: CTs, Voltage Leads, Ground Probes & Leads, PC software and download cable are included with this product.
  • Works with single and three phase systems (Y and Delta)
  • Detects and records voltage anomalies, Sags and Surges
  • Built in scope displays waveforms
  • Phase sequence indication
  • Records up to 64 parameters (single or three phase) simultaneously
  • Manual and programmable recording start
  • Password protection
  • Selectable fundamental frequency of 50 or 60 Hz
  • Special data compression system and user selectable rates allow recording from several hours to several years
  • Download capabilities, Windows compatible PC software
  • Displacement power factor for power factor correction determination
  • Line or battery powered
  • Megohmmeter functions: Tests insulation of wires, cables, transformers and electrical motors
  • Selectable test voltages up to 1000V
  • Programmable timer to perform the Dielectric Absorption Ratio Test
  • Sensitive Ohmmeter for checking resistance of motor windings
  • Selectable polarization of ohmmeter for checking grounding continuity
  • Automatic voltmeter protects against misuse on hazardous energized systems
Supplied Current Transducer:    DM-CT-HTA 1000A Standard CT 2” internal diameter CT +/-(0.5% Rdg + 2 LSD
AC Current:    DM-CT-100:0.5A to 100A / DM-CT-HTA:5 - 1000A /AM-FLEX33: Selectable: 5 – 1000A or 15 - 3000A +/-(0.5% Rdg + 2 LSD)
AC Voltage including Sags and Surges:    0 - 600V +/-(0.5% Rdg + 2 LSD
Harmonics:    THD, DC and individual up to 49th +/-(0.5% Rdg + 2 LSD)
Power:    Working (W), Reactive (VAR) and Apparent (VA) +/-(1.0% Rdg + 2 LSD
Energy:    Working (kWh), Reactive (VARh) and Apparent (VAh) +/-(1.0% Rdg + 2 LSD)
Peak Demand:    KW +/-(1.0% Rdg + 2 LSD)
Power Factor:    0.00 – 1.00
Frequency Measurement:    57 to 63.6 Hz at 60Hz fundamental 47 to 53 Hz at 50Hz fundamental +/-(1.0% Rdg + 2 LSD)
Phase Sequence:    1/2/2003
Co-generation    Computes incoming and outgoing energy
Selectable Fundamental Frequencies    50/60 Hz
Available Recording Time    Several hours to several years depending on setup
Insulation resistance with 50 VDC test voltage    0.01-19.99, 49.9 +/- (2% Reading + 2 digits) 49.9 - 99.9MΩ +/- (5% Reading + 2 digits)
Insulation resistance with 100 VDC test voltage    0.01-19.99, 99.9 +/- (2% Reading + 2 digits) 99.9 - 199.9MΩ +/- (5% Reading + 2 digits)
Insulation resistance with 250 VDC test voltage    0.01-19.99, 199.9, 249 +/- (2% Reading + 2 digits) 249 - 499MΩ +/- (5% Reading + 2 digits)
Insulation resistance with 500 VDC test voltage:    0.01-19.99, 199.9, 499 +/- (2% Reading + 2 digits) 499 - 999 MΩ +/- (5% Reading + 2 digits)
Insulation resistance with 1000 VDC test voltage:    0.01-19.99, 199.9, 999 +/- (2% Reading + 2 digits) 999 - 1999 MΩ +/- (5% Reading + 2 digits)
Low resistance (without timer):    0.01-19.99, 99.9Ω+/- (2% Reading + 2 digits)
Low resistance (with timer):    0.01-9.9Ω+/- (2% Reading + 2 digits)
Ground resistance:    0-19.99, 199.9, 1999 Ω +/- (5% Reading + 3 digits)
Ground resistivity:    0.6- 125.6 Ωm 0.125-1.256, 19.99, 199.9 kΩm +/- (5% Reading + 3 digits)
Model NameDescription
DM-III Multitest
  • Power Quality Analyzer/ Data Logger: True RMS (TRMS)
  • Works with single and three phase systems (Y and Delta)
  • Records up to 64 parameters (single or three phase) simultaneously
  • Megohmmeter functions:Selectable test voltages up to 1000V
  • Ground Resistance and Resistivity functions:Three measuring modes
  • Phase sequence indication
  • Compatible with wide range of Current Transducers, DM-CT-HTA supplied
Included Accessories:   External power supply, users manual,test leads,ground resistance test leads with 4 ground stakes,carrying case,PC software and USB cable,3 current transducers (1000 amps)

Current Transducers
DM-CT-100Amprobe DM-CT-100 Current Transducer
DM-CT-HTAAmprobe DM-CT-HTA Clamp Attachment
Search
Find Resources
Find Products
Related Products

 Write the first review
 
 Amprobe DM-III Multitest F 3000A Power Quality Recorder »

Follow us  Google+       Home  |  About Us  |   Privacy Statement  |  Site Map  |   Contact Us© 1995 - 2017 Amprobe