Diagnose potential failure with the MO-100, portable battery powered milliohm meter. Quickly check windings opens or shorts in motors, generators and transformers, wire-to-wire connection resistances, heating elements testing and contact resistance in critical electrical connections.

|
Amprobe MO-100 Milliohm Meter
5
5
2
2
Very useful in the HVAC/R Trade.
I used this tool to prevent major calls in the middle of the night. Its helps me generate sales to customers. I show them that their compresors, motors, transformers are about to go out, and most of them want to change the bad part with in a day or two. Of course, I had customers who have wished to listen to me.
March 29, 2012
Excellent Value
This meter enabled us to isolate and identify a defective appliance cord that was causing nuisance CAFCI trips. Isolation did not work, failures were minimum 4 days apart.
Moving the load stopped the failures (cord flexed differently). This is now a new weapon in our troubleshooting arsenal.
February 29, 2012
|
- Accurate four terminal measurement down to 100µ ohms does not require test leads resistance compensation
- Ranges from 200.0m ohms to 2000 ohms with minimum resolution of 100µ Ohm
- Measurement precision with three test currents with over-temperature protection
- Protection against inadvertent connection to overvoltage
- Large LCD
- Potential lead resistance, current lead resistance checks
- Auto-hold and auto-off features
- Lightweight, robust & compact.
- Indicates measurement errors due to temperature or connection problems
- “O-Ring sealed enclosure
- Battery powered
- IEC / EN 61010-1
- Test leads, Instruction manual, Shoulder belt, 1.5V(AA) x 8 Batteries
|
| Measuring range |
0 → 200.0 mO in steps of 100 µO
0 → 2000 mO in steps of 1 mO
0 → 20.00 O in steps of 10 mO
0 → 200.0 O in steps of 100 mO
0 → 2000 O in steps of 1 O |
| Test current |
1 mA (2000 O range)
10 mA (20 O / 200 O range)
100 mA (200 mO / 2000 mO range) |
| Specifications |
| Measuring ranges: |
0-200.0m ohms in steps of 100µohm
0-2000m ohms in steps of 1m ohm
0-20.00 ohms in steps of 10m ohm
0-200.0 ohms in steps of 100m ohm
0-2000 ohms in steps of 1 ohm |
| Accuracy: |
±0.5% of reading ±2 digits over the operating temperature range, -15°C to 55°C (5°F to 131°F), with the supplied test leads |
| Test current: |
1mA =>2000 ohms range
10mA =>200/ 20 ohms range
100mA =>2000m / 200m ohm range |
| Accuracy: |
±0.1% |
| Protection fuses: |
Mains = 0.5A, HBC, 5 x 20mm, DIN
Current = 0.5A, HBC, 5 x 20mm, DIN
Voltage = 0.5A, HBC, 5 x 20mm, DIN
Maximum output
Voltage (C1-C2) 20V |
For complete specs please download the product datasheet under the “Resources" tab.
|
| Model Name | Description | Price List | | MO-100 | - Accurate four terminal measurement down to 100µ ohms does not require test leads resistance compensation
- Ranges from 200.0m ohms to 2000 ohms with minimum resolution of 100µ Ohm
- Measurement precision with three test currents with over-temperature protection
Included Accessories: Users manual, test leads, batteries (installed) |
|
|
|
|